Load-generation balance and system inertia are essential for maintaining frequency in power systems. Power grids are equipped with Rate-of-Change-of-Frequency (ROCOF) and Load Shedding (LS) relays in order to keep load-generation balance. With the increasing penetration of renewables, the inertia of the power grids is declining, which results in a faster drop in system frequency in case of load-generation imbalance. In this context, we analyze the feasibility of launching False Data Injection (FDI) in order to create False Relay Operations (FRO), which we refer to as FRO attack, in the power systems with high renewables. We model the frequency dynamics of the power systems and corresponding FDI attacks, including the impact of parameters, such as synchronous generators’ inertia, and governors’ time constant and droop, on the success of FRO attacks. We formalize the FRO attack as a Constraint Satisfaction Problem (CSP) and solve using Satisfiability Modulo Theories (SMT). Our case studies show that power grids with renewables are more susceptible to FRO attacks and the inertia of synchronous generators plays a critical role in reducing the success of FRO attacks in the power grids.

Recommended citation: Jafari, M., Shahriar, M. H., Rahman, M. A., & Paudyal, S. (2021, July). False relay operation attacks in power systems with high renewables. In 2021 IEEE Power & Energy Society General Meeting (PESGM) (pp. 01-05). IEEE.
Download Paper